11/22/2019
Industry has been using controllers for years. In 1911 the first PID (Proportional - Integral - Derivative) control was created and it is still widely used in automation. In this article, we will present the theory and equation behind each controller action to understand its operation.
Around the 18th century, the industry used controllers with mechanical feedback for process control. Generally, the controllers had only two actions of the Proportional, Integral and Derivative set, but never the three of them. At that time, the devices controlled the actuating speed of steam engines and aimed to provide greater stability to industrial machines operation.
In 1911, the businessman and inventor Elmer Sperry created the PID control (Proportional – Integral – Derivative), which combines these three actions. Sperry designed this controller for the United States Navy. He aimed to automate ship steering and emulate the behavior of a helmsman, who was capable of compensating persistent variances and predict future variations in the high seas. A few years after this creation, the engineer Nicolas Minorsky published the first theoretical analysis of PID control, describing its behavior in a mathematical formula that is used as a basis for calculation until today.
Currently, in the business field, it is possible to measure efficiency in different processes and in various ways. Each sector has goals, indicators and results. In addition, control is carried out to obtain results and seek the best efficiency in the use of resources. Control loops and algorithms are employed to guarantee that the manufacturing system of an industry operates by exploiting its limits within an acceptable pattern of use.
Nowadays, even with the most advanced control techniques available, PID controllers are the most used option in processes loops (BAZANELLA, 2005), such as petrochemical, cellulose, dairy or water treatment companies, among others. When well configured (manual mode), this PID Control can anticipate, reduce and even eliminate noises, which makes it desirable. Sometimes, the manual configuration of PID parameters requires expertise and prior theoretical knowledge from those who operate the device to find the best control for the process. According to Aström; Hägglund (1995), estimations indicate that about 90% of control loops in industrial processes operate with this controller.
We call the system to be controlled in the industry as a plant or process, the signal applied to the process input as a control signal or manipulated variable (MV), and the output signal of the process as a controlled variable or process variable (PV). In order to achieve maximum process efficiency, a controller is used at the process input, which receives an input reference or setpoint (SP) and ensures the stability of the output signal.
In a systems process with output feedback, a loop is formed. This arrangement is called a “closed-loop”. In the closed-loop system, the controller constantly receives the difference between the SP and the actual value of PV. This difference is called Error and, based on it, the device creates a control signal to decrease the error to a small error or zero value (OGATA, 1982), regardless of whether there is a signal of disturbance in the process or not. The closed-loop control increases the accuracy of the control system and the rejection of disturbance effects on PV, decreases variation through instabilities and increases robustness.
*Erro = error
*Processo = process
The PID control combines Proportional, Integral and Derivative actions to create a control signal, where each action has a strong characteristic that helps to control the output: The Proportional action makes the system respond to the present error and enables immediate action in the face of variations or disturbances; the Integral action eliminates errors such as jumps or steps in a permanent and long term regime; and the Derivative action anticipates the behavior of the process (BAZANELLA, 2005).
Because of the restriction of physical order and security, there is an upper and lower limit to the application of the MV signal. This operating range is called the Proportional Band. If the control signal operates outside the limits, it is saturated and operates with non-linear behavior. The higher the Proportional action value, the lower the Proportional Band and the higher the control power. That makes the system to respond with greater speed, but the output signal can exceed or fall below the setpoint in permanent mode and the error will never be completely overturned.
When Integral action is applied in an isolation way, it worsens the relative stability of the system. When used in conjunction with the Proportional action, it helps to annul the error in a permanent mode. The higher the Integral value, the longer it takes for the system to reach the setpoint in a permanent mode.
*Início da ação integral = Integral action starting
The process usually has inertia in relation to changes in MV, that is, the time that a change in the process input causes a change in the output. The Derivative action anticipates the control action so that the process reacts faster than usual. This predictive action increases the relative stability of the system and makes the response faster and less oscillatory according to the derivative time. In a permanent mode, this action will be null because the error value will be constant.
The mathematical equation to calculate the MV control signal is shown below. In it, the Kp, Ti and Td parameters are related. The Error value, presented as “e” in the equation, it is used by each control action to create the signal.
*Control Signal
Thus, the PID control combines the three actions described above and each one compensates for the undesirable characteristic of the other. The Integral action in permanent mode makes the error null and the oscillatory effect of the Integral action is suppressed by the Derivative action, because the anticipated effect makes the response faster and increases the relative stability of the system. The Proportional action changes the speed with which the configured setpoint is pursued. These behaviors can be observed when you individually increase the value of each action in the process.
The PID relevance continues to be satisfactory over time. Many devices in the automation field are already marketed with this control as an operational option. Currently, several NOVUS products already have the PID control as a native function, such as, for example, the N1030 controller, the N1200 controller, the N2000 controller, among others. Besides offering manual adjustment of the PID parameters, NOVUS controllers also offer the PID self-adaptive feature, where the device identifies the process of the client and auto-configures the best values for the Proportional, Integral and Derivative parameters, looking for a satisfactory control.
References:
Alpi, Lucas Brollo. “Desenvolvimento de uma Planta Didática para o Controle de Nível de Tanques Acoplados”.
Aström, K. J.; Hägglund, T. H. “PID Controllers”: theory, design and tuning. 2.ed. Research Triangle Park, Instrument Society of America, 1995.
Bazanella, A. S.; Silva Júnior, J. M. G. Da. “Sistemas de Controle”: princípios e métodos de projeto. 1.ed. Editora UFRGS, 2005.
Bennett, Stuart. “Development of the PID Controller”.
Dillenburg, Marcos R. “Indo Além do Controle P.I.D.”.
Ogata, K. “Engenharia de Controle Moderno”. Editado por André Fábio Kohn, José Carlos Teixeira de Barros Moraes. Editora Prentice/Hall do Brasil Ltda, 1982.
9/30/2024
NOVUS will be present at four important fairs in October 2024, presenting its innovative technological solutions for different industry sectors. Check out event details and featured products:
8/26/2024
Software and firmware upgrades benefit complex applications and more...
7/25/2024
International Trade Show is Southeast Asia's biggest Automation Industry Exhibition
6/26/2024
As an innovative company, NOVUS develops the best solutions in line with solid market trends.
6/17/2024
New LogBox uses Long-Term Evolution technology